Thermo graphic report

 

Inspected by

APE

Inspected date

15thMay 2019

Equipment

High Voltage Terminal 22 kV

 

High Voltage Terminal Phases A,B,C

 
Area Temperature ºC Temperature ºC Current Phase A,B,C Delta Temp ºC Result
a-b 31 31.1   - 0.1 Normal
a-c 31 31   0 Normal
b-c 31.1 31   0.1 Normal

 

Result

The temperature detected from the at high voltage terminal 22 kV phase A phase B and phase C of are within the normal operating value.

 

Recommendation

Periodic infrared thermal inspection should be tested every year.